EasyManua.ls Logo

Simplex 4100ES - Analyzing Self-Test Results

Simplex 4100ES
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
64
___________________________________________________________________________
Once the Self-Test is complete, the panel will display the test results and group the
devices into different categories.
Consult Table 8-4 for the explanation of the various diagnostics:
Table 84. View Results Options
Category
Diagnostic
Definition
User Action
Passed
Normal
The test results indicate that the
appliance component is functioning
properly.
N/A
Failed
No Output
The audible or visual sensor did not
detect any sound or light from the
appliance.
To clear the trouble* the
appliance must be repaired
and re-tested. A panel
hardware reset will reset
the pseudo but will not
automatically clear the
trouble.
No Result /
Not Tested
-The appliance did not return a result
before the test ended.
-The test was deactivated for a tested
component. For example, if the “Volume”
option is set to “Silent”, all audible (horn
or speaker) components will display this
result.
This trouble* can be cleared
by performing a panel
hardware reset.
Unsupported
Unsupported
The appliance tested is a legacy
notification appliance and is not
compatible with the TrueAlert ES Self-
Test.
N/A
*Troubles will only be triggered if the “Trouble on Fault” option is set to “Yes”.
_______________________________________________________________________________
TrueAlert ES Appliance Self-Test , Continued
Analyzing Self-Test
Results

Table of Contents

Other manuals for Simplex 4100ES

Related product manuals