34
Alarm, high pressure
If the line pressure is not low enough at the beginning of pressurisation, the code AHP will be blinking on the display and
the red LED L1 or L2 of the line that triggered the alarm will be blinking.
In pressure transmitter operation, an alarm is triggered if the line pressure is above the set low limit when
pressurisation starts. Pressurisation will restart for the same line when the pressure level has fallen below the
low limit
value and the alarm has been acknowledged by pressing SET.
In pressure switch operation, an alarm is triggered if the pressure switch is closed when pressurisation starts.
Pressurisation will restart for the same line when the pressure switch opens and the alarm has been acknowledged by
pressing SET.
Alarm, low pressure
If the line pressure does not rise high enough during pressurisation, the code ALP will be blinking on the display and the
red LED L1 or L2 of the line that triggered the alarm will be blinking.
In pressure transmitter operation, an alarm is triggered if the line pressure does not reach the set high limit within the
set maximum pressurisation time. Pressurization will restart for the same line when the alarm has been acknowledged by
pressing SET.
In pressure switch operation, an alarm is triggered if the line pressure switch does not close within the set maximum
pressurisation time. Pressurization will restart for the same line when the alarm has been acknowledged by pressing SET.
Pulse alarm, ProFlex lubrication system
The channel will trigger the pulse alarm ALP (Alarm Low amount of Pulses) and go into the alarm mode if the number of
pulses is not reached within the set maximum pressurisation time.
Alarm from SKF Doser monitor operation indicator
The SKF Doser monitors are in use when the factory setting parameter LGI has been set to YES.
An alarm will be triggered when the SKF Doser monitor does not recognise doser operation during a lubrication cycle.
The code AIn will be displayed. Lubrication continues normally despite the alarm. This feature is different from any other
alarms. The alarm can be acknowledged by pressing SET.
Alarm from the air pressure switch of the grease spray system
Air pressure control is in use when the factory setting parameter AC has been set as YES.
In a progressive system, the channel spray control starts always when the pump is running. The pump stops when
the pulse amount has been reached. The spray control remains on for 10 seconds
An alarm will be triggered if the air pressure switch is not open when pressurisation starts or closed when pressurisation
has stopped. The code Air will be displayed. Pressurisation will restart for the same line when the alarm has been
acknowledged by pressing SET.
Warning of pump change (Dualset)
When a dual pumping centre (Dualset) is in use, the display will show the warning message APC when the pump has
been automatically changed. Lubrication will continue normally regardless of the warning. The warning can be
acknowledged by pressing SET. The alarm output will not be activated in this case.