Troubleshooting
Service Manual
SKOPE Reflex Upright Fridge, Freezer, Combo
7 Troubleshooting
Electronic Controller
Alarms signal unexpected operational changes in the cabinet or cartridge.
When an alarm is activated, use the electronic controller app to assist with
fault diagnosis and service as necessary. See page 14 for information.
General Operation
For problems with the cabinet and refrigeration cartridge use the following
table. Refer to relevant section in this service manual for safe access to
perform repair.
Problem Possible Cause Repair
• Cabinet not operating.
• No controller display.
• Loss of power supply. • Check mains power
supply.
• Loose plug. • Check all plugs are
connected correctly.
• Lights not on. • See “Lighting” on page 32.
• Excess noise vibration. • Refrigeration pipes
transferring vibration into
cartridge.
• Re-align pipes.
• Fan hitting shroud. • Re-align motor mounting.
• Frozen evaporator coil. • Set-point is too cold. • Check and raise.
• Evaporator probe fault. • Check and replace
evaporator probe.
• Controller fault. • Replace controller.
• Short of refrigerant. • Perform refrigeration
system diagnostics and
service as required.
• Power consumption is
higher than expected.
• Cartridge operating too
hot.
• Clean the condenser.
• Ensure the cabinet has
good ventilation around
the refrigeration
cartridge.
• Ensure the cabinet is
within the maximum
operating temperature.
• Frequent door opening. • Limit door openings.
• Set point to low. • Raise set point.
Continued over page