BlueControl Insect
24 Technical User Guide
5.3 Auxiliary
5.3.1 Auxiliary sensor alarm
Menu button | Settings | Alarms | Auxiliary
Auxiliary sensors The controller triggers an alarm if the values for the sensor fall below or exceed
the setpoints.
5.3.2 Auxiliary alarms
It is possible to create a number of auxiliary alarms. For example, the controller may give an alarm from a con-
nected motor controller, a water pump or other equipment.
The alarms can be sorted within each column by pressing the heading.
Menu button | Settings | Alarms | Auxiliary | Auxiliary alarm settings
Press Add to add a new alarm.
Press Name to name the alarm.
Press Category to add the alarm to a category.
Select the alarm type Hard, Soft or Disabled.
Set a delay, if required. In this way, the alarm signal can be de-
layed so that the alarm is not triggered when the alarm limit is
briefly exceeded.
Set the activation to take place in the event of high or low input.
Select if the alarm should be active always or from a specific
day number.
To delete an auxiliary alarm, press the icon .
After creating the alarm, see the menu | Installation | Show connection for information about where to
connect the extra equipment.
5.4 Master/Client alarms
If the controller is set up to share equipment with other controllers, it gives an alarm if the connection between
the controllers is lost. A ‘Client’ controller will continue to regulate according to the latest received value from the
‘Master’ controller equipment until the network connection is restored.
Menu button | Settings | Alarms
Connection to Client lost
Connection to Master lost
Select the alarm type Hard, Soft or Disabled.
5.5 Emergency control
5.5.1 Emergency opening
Emergency opening is a standard function in the controller . The controller will activate the ventilation system in
case of a relevant alarm, see the levels in section Control parameters [}47].
Activated by CE
Pressure low alarm
Yes
Pressure high alarm
Yes