BlueControl Insect
Technical User Guide 49
Requirement at
low sensor failure
Required ventilation if the pressure sensor gives alarm for low pressure.
Requirement at
high sensor failure
Required ventilation if the pressure sensor gives alarm for high pressure.
11.6 Adjustment of pressure
11.6.1 Adjustment of stepless unit
For the controller to set the correct relation between the fan voltage and the flap position and thereby supply the
correct ventilation, it is important the the stepless units are correctly set. This is also important to maintain pres-
sure stability.
Fan Output Flaps
0.0
58.0
58.0
54.0
55.0
55.0
100.0
100.0
0.0
15.0
25.0
45.0
55.0
85.0
90.0
100.0
0.0
32.0
41.0
58.0
66.0
86.0
85.0
100.0
Table2: Curve values for stepless unit
The air outlet’s flap position and fan speed %
Output %
Flap %
Vent %
Vent [%] Fan voltage
Output [%] Output for the stepless fan
Flap [%] Flap position for air outlet
With Dynamic MultiStep, two set-ups must be carried out for the stepless units for low regulation and high regu-
lation respectively. Also see section Dynamic MultiStep [}29]