BlueControl Insect
34 Technical User Guide
Runs before recalibration Setting of the number of times the inlet flap has to run before it calibrates
automatically.
Minimum voltage
Maximum voltage
When the air outlets are 0-10 V controlled, the output voltage can be ad-
justed via the min. voltage as well as th max. voltage.
In the menu Technical | Calibration | Central exhaust | Central exhaust air outlet flap.
Select ON to start the calibration.
Check that the correct flap(s) open(s) and close(s) correctly.
Wait until the calibration is completed and the display shows Ended again.
Carry out the calibration in the same way for air outlet 2.
Auxiliary sensors
For auxiliary sensor the units for Minimum value and Maximum value will depend on which kind of sensors
have been selected. Besides ppm, the units can be Pa, °C, % and m/s.