HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 26 of 65
Magnetic Pickup
Shielding
Connected with Speed sensor, shielding line is
recommended. (B-) has already connected with
speed sensor 2.
Ground connected is active (B-)
Normally close outputs, rated 7A
Normally open outputs, rated 7A
Impedance-120Ω shielding wire is recommended,
its single-end earthed.
Impedance-120Ω shielding wire is recommended,
its single-end earthed.
Shielding line is recommended. Shielding layer
connect to earth at GOV end.
Shielding line is recommended. Shielding layer
connect to earth at AVR end.
Impedance-120Ω shielding wire is recommended,
its single-end earthed.
Normally close outputs, rated 7A
Normally open outputs, rated 7A
Normally open outputs, rated 7A
Bus A-phase voltage
sensing input
Connected to A-phase of bus (2A fuse is
recommended)
Bus B-phase voltage
sensing input
Connected to B-phase of bus (2A fuse is
recommended)
Bus C-phase voltage
sensing input
Connected to C-phase of bus (2A fuse is
recommended)
Connected to N-wire of bus
Gen-set A-phase
voltage sensing input
Connected to A-phase of gen-set (2A fuse is
recommended)
Gen-set B-phase
voltage sensing input
Connected to B-phase of gen-set (2A fuse is
recommended)
Gen-set C-phase
voltage sensing input
Connected to C-phase of gen-set (2A fuse is
recommended)
Connected to N-wire of gen-set