HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 35 of 65
No.
Items
Parameters
Defaults
Description
Sync Setting -Basic
1
Dead Bus Volt
(10-50)V
30
It is considered Bus no power when Bus
voltage is lower than dead Bus voltage.
2
Voltage Difference
(0-30)V
3
It is considered voltage synchronization
when the voltage difference between
Generator and Bus is lower than
synchronization voltage difference.
3
Positive Freq
Difference
(0-2.0)Hz
0.2
It is considered frequency
synchronization when the frequency
difference between Generator and Bus
is less than Check Up Freq but more
than Check Low Freq .
4
Negative Freq
Difference
(0-2.0)Hz
0.1
5
Phase Angle
Difference
(0-20)°
10
It is considered Check Phase Angle
when the initial phase difference is lower
than synchronization phase difference.
6
Slip Frequency
(0-1.00)Hz
0.10
Adjust generator frequency and enable it
greater than Bus frequency.
7
MSC ID
(0-31)
1
It is the ID mark of the MSC
communication internet. All the MSC
ID should be unique.
8
MSC Priority
(0-31)
0
Smaller values represent higher
priorities.
9
Full kW rating
(0-20000)kW
276
Used for load sharing.
10
Full kVar rating
(0-20000)kvar
210
Used for load sharing.
11
Baud Rate
(0-3)
1
0500kbps1250kbps
2125kbps350kbps
12
Scheduled Run
PCT
(0-100)%
80
Schedule the load value of other genset
when start on demand.
13
Scheduled Stop
PCT
(0-100)%
50
Schedule the load value of other genset
when start on demand.
14
Load Ramp Rate
(0.1-100.0)%
3.0
Speed rate(%/s) of genset
upload/unload
15
Load Ramp Point
(0.1-40.0)%
10.0
16
Load Ramp Delay
(0-30)s
0
17
Starting Options
(0-1)
1
0Start All Sets1Start Sets as Load
Requires
18
MSC Modules
(2-10)
2
Action Type:
0No Action1Warn2Trip.
19
MSC Too Few
Modules Action
Type
(0-2)
1
20
Balance Engine
Hours
(1-1000)Hours
Disable
When the input is active, the controller
will start/stop the genset automatically
according to the running time and the
pre-set balanced running time.
21
Fail to Sync Delay
(5.0-300.0)s
60.0
When the controller detects no Sync