HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 36 of 65
No.
Items
Parameters
Defaults
Description
22
Fail to Sync Action
(0-1)
0
signal during the preset delay, it will
send corresponding alarm signal
according to the action type.
Action Type:
0Warn1Trip.
23
NEL (Load
Shedding) Trip
(0-1)
0
0: Disable 1: Enable;
Details of function description please
see the following.
24
NEL Trip 1 Set
Value
(0-200)%
90%
25
NEL Trip 1 Delay
(0-3600)s
5
26
NEL Trip 2 Set
Value
(0-200)%
100%
27
NEL Trip 2 Delay
(0-3600)s
1
28
NEL Auto
Reconnection
(0-1)
0
29
NEL Auto
Reconnection Set
Value
(0-200)%
50%
30
NEL Auto
Reconnection
Delay
(0-3600)s
5
31
NEL Load
Shedding Number
(1-3)
3
Sync Setting - GOV
1
Output Type
(0-1)
1
0Relay output1Analog Voltage
Output
2
Output Reverse
(0-1)
0
0Disable1Enable.
3
Action
(0-2)
1
0None1Adjust to Rated Frequency
2Adjust to Center Point
4
Center Voltage
SW1
(0-10.0)
0
Default central voltage: 0V.
5
Voltage Range
SW2
(0-10.0)
2.0
Default volt. range: (-2.5~+2.5)V
6
Sync Gain
(0-500)
20
Adjust and control before paralleling.
7
Sync Stability
(0-2000)
20
Adjust and control before paralleling.
8
Load Gain
(0-500)
20
Adjust and control after paralleling.
9
Load Stability
(0-2000)
20
Adjust and control after paralleling.
Sync Setting - AVR
1
Output Type
(0-1)
1
0Relay output1Analog Voltage
Output
2
Output Reverse
(0-1)
0
0Disable1Enable.
3
Action
(0-2)
1
0None1Adjust to Rated Frequency
2Adjust to Center Point
4
Center Voltage
SW1
(0-10.0)
0
Default central voltage: 0V.