HGM9510 GENSET PARALLEL UNIT 
HGM9510 Genset Parallel Unit ISSUE 2013-08-06     Version 1.1 Page 37 of 65 
Default volt. range: (-2.5~+2.5)V 
Adjust and control before paralleling. 
Adjust and control before paralleling. 
Adjust and control after paralleling. 
Adjust and control after paralleling. 
0:    3P4W; 1:    3P3W;   
2:    2P3W; 3:    1P2W. 
To  offer  standards  for  detecting  of 
mains’  over/under  voltage  and  loading 
voltage.  (It  is  primary  voltage  when 
using  voltage  transformer;  it  is  line 
voltage when AC system is 3P3W while 
it is phase voltage when using other AC 
system). 
To  offer  standards  for  detecting  of 
over/under/load frequency. 
Setting  value  is  percentage  of  mains 
rated  volt.  Delay  value  (default:  0.1s) 
and      alarm  action  (default:  trip  and 
stop) also can be set. 
Setting value is mains rated frequency’s 
percentage.  Delay  value(default:  0.1s) 
and alarm action (default: trip and stop) 
also can be set. 
Setting value is mains’ rate of change of 
frequency, and alarm action (default: trip 
and stop) and delay value (default: 0.1s) 
also can be set. 
Setting  value  is  phase  angle’s  change 
rate  of  mains  voltage  waveform,  and 
alarm action (default: trip and stop) and 
delay value  (default:  0.1s) also  can be 
set. 
Note:overcurrent setting details about definite time delay and inverse definite minimum time. 
Definite  Time : overcurrent  delay  is  definite  time  delay.  Different  overcurrent  value  has 
corresponding delay.   
Inverse  Definite  Minimum  Time(IDMT) : overcurrent  delay  decrease  with  the  increase  of 
overcurrent. Different overcurrent value has corresponding delay.   
IDMT formula: