HGM9510 GENSET PARALLEL UNIT
HGM9510 Genset Parallel Unit ISSUE 2013-08-06 Version 1.1 Page 37 of 65
No.
Items
Parameters
Defaults
Description
5
Voltage Range
SW2
(0-10.0)
2.0
Default volt. range: (-2.5~+2.5)V
6
Sync Gain
(0-500)
20
Adjust and control before paralleling.
7
Sync Stability
(0-2000)
20
Adjust and control before paralleling.
8
Load Gain
(0-500)
20
Adjust and control after paralleling.
9
Load Stability
(0-2000)
20
Adjust and control after paralleling.
Mains Split Setting
1
AC System
(0~3)
0
0: 3P4W; 1: 3P3W;
2: 2P3W; 3: 1P2W.
2
Rated Voltage
(30~30000)V
230
To offer standards for detecting of
mains’ over/under voltage and loading
voltage. (It is primary voltage when
using voltage transformer; it is line
voltage when AC system is 3P3W while
it is phase voltage when using other AC
system).
3
Mains Rated
Frequency
(10.0~75.0)Hz
50.0
To offer standards for detecting of
over/under/load frequency.
4
Volt. Trans.(PT)
(0-1)
0
0: Disable ; 1: Enable
5
Mains Over
Voltage
(0-200)%
105%
Setting value is percentage of mains
rated volt. Delay value (default: 0.1s)
and alarm action (default: trip and
stop) also can be set.
6
Mains Under
Voltage
(0-200)%
95%
7
Mains Over
Frequency
(0-200)%
105%
Setting value is mains rated frequency’s
percentage. Delay value(default: 0.1s)
and alarm action (default: trip and stop)
also can be set.
8
Mains Under
Frequency
(0-200)%
95%
9
ROCOF
(0-1.00)Hz/s
0.20
Setting value is mains’ rate of change of
frequency, and alarm action (default: trip
and stop) and delay value (default: 0.1s)
also can be set.
10
Vector Shift
(0-20.0)°
6.0
Setting value is phase angle’s change
rate of mains voltage waveform, and
alarm action (default: trip and stop) and
delay value (default: 0.1s) also can be
set.
Noteovercurrent setting details about definite time delay and inverse definite minimum time.
Definite Time overcurrent delay is definite time delay. Different overcurrent value has
corresponding delay.
Inverse Definite Minimum Time(IDMT) overcurrent delay decrease with the increase of
overcurrent. Different overcurrent value has corresponding delay.
IDMT formula: