HGMS62 Split Type Genset Controller User Manual Page 17 of 58
6.2 SHUTDOWN ALARMS
When controller detects shutdown alarm, it will send signal to open breaker and stop genset. The
alarms are displayed in LCD.
Table 7 – Shutdown Alarms
When controller detects emergency stop signal, it will send shutdown
alarm signal.
When genset speed is higher than threshold, controller will send
shutdown alarm signal.
When genset speed is lower than threshold, controller will send
shutdown alarm signal.
When speed is 0 and speed signal loss action selects “Shutdown”,
controller will send shutdown alarm signal.
When genset frequency is higher than threshold, controller will send
shutdown alarm signal.
When genset frequency is lower than threshold, controller will send
shutdown alarm signal.
When genset voltage is higher than threshold, controller will send
shutdown alarm signal.
When genset voltage is lower than threshold, controller will send
shutdown alarm signal.
Within set start times, if fails to start, controller will send shutdown alarm
signal.
When genset current is higher than threshold and overcurrent action
selects “Shutdown”, it will send shutdown alarm signal.
When maintenance countdown is 0 or maintenance date is due,
maintenance due action selects “Shutdown”, controller will send
shutdown alarm signal.
When reverse power value (power is negative) is higher than threshold,
and reverse power action selects “Shutdown”, controller will send
shutdown alarm signal.
When power value (power is positive) is higher than threshold, and over
power action selects “Shutdown”, controller will send shutdown alarm
signal.
When temperature sensor is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
When temperature value is higher than threshold, controller will send
shutdown alarm signal.
When oil pressure sensor is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
When oil pressure value is lower than threshold, controller will send
shutdown alarm signal.