HGMS62 Split Type Genset Controller User Manual Page 18 of 58
When level sensor is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
When level value is lower than threshold, controller will send shutdown
alarm signal.
When aux. sensor 1 is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
When aux. sensor 1 value is higher than threshold, controller will send
shutdown alarm signal.
When aux. sensor 1 value is lower than threshold, controller will send
shutdown alarm signal.
When aux. sensor 2 is open and open action selects “Shutdown”,
controller will send shutdown alarm signal.
When aux. sensor 2 value is higher than threshold, controller will send
shutdown alarm signal.
When aux. sensor 2 value is lower than threshold, controller will send
shutdown alarm signal.
When digital input is active for shutdown alarm, controller will send
shutdown alarm signal.
6.3 TRIP AND STOP ALARMS
When controller detects trip and stop alarm signal, it will disconnect gen close signal immediately
and stop after cooling.
Table 8 – Trip and Stop Alarms
When genset current is higher than threshold and overcurrent action
selects “Trip and Stop”, controller will send trip and stop alarm signal.
When maintenance countdown is 0 and maintenance date is due,
maintenance due action selects “Trip and Stop”, controller will send trip
and stop alarm signal.
When genset reverse power value (power is negative) is higher than
threshold, and reverse power action selects “Trip and Stop”, controller
will send trip and stop alarm signal.
When genset power value (power is positive) is higher than threshold,
and over power action selects “Trip and Stop”, controller will send trip
and stop alarm signal.
When input port is configured as “Trip and Stop” and active, controller
will send trip and stop alarm signal.