- 97 -
No.EX##-OMY0004
Error codes for F parameter errors
Code
Additional Information
Brief Description
Solution
0x0040
64dez
None
The parameterised
F_destination_address
does not coincide with
the PROFIsafe
address set on the
safety module (F
module).
Profisafe address on the safety module and value
in the F_destination_address must be made to
coincide.
0x0041
65dez
None
Invalid
parameterisation of the
F_destination_address.
The addresses 0x0000
and 0xFFFF are not
permitted.
Correct the value.
0x0042
66dez
None
Invalid
parameterisation of the
F_source_address.
The addresses 0x0000
and 0xFFFF are not
permitted.
Correct the value.
0x0043
67dez
None
Invalid
parameterisation of the
F_WD_time. A
monitoring time of 0
ms is not permitted.
Correct the value.
0x0044
68dez
None
Invalid
parameterisation of the
F_SIL. The required
SIL cannot be
supported by the
safety module (F
module).
Use the device with the required SIL. The safety
module reaches SIL 3 as a maximum.
0x0045
69dez
None
Invalid
parameterisation of the
F_CRC_length. The
CRC length generated
by the safety module
(F module) does not
correspond to the
required length.
Check device description.
0x0046
70dez
None
F parameter set
version is invalid. The
version of the safety
module (F module)
does not coincide with
the required version.
Check device description.
Only V2 mode permitted.