EasyManua.ls Logo

SMC Networks EX245-FPS1

SMC Networks EX245-FPS1
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 96 -
No.EX##-OMY0004
Code
Additional Information
Brief Description
Solution
0x035X
848dez
849dez
850dez
851dez
The least significant four bits
display information on the
affected input.
Range of values:
0: IN0, IN4
1: IN1, IN5
2: IN2, IN6
3: IN3, IN7
The value for the
symmetry monitoring
is outside the
permitted range of
values.
For the displayed input pair the value for the
symmetry monitoring (discrepancy time) is not in
the permitted range.
Set the discrepancy time to ‘NO LIMITand resend
the parameter data to the device.
0x03CX
960dez
961dez
962dez
963dez
The least significant four bits
display information on the
affected input pair.
Range of values:
0: IN0, IN4
1: IN1, IN5
2: IN2, IN6
3: IN3, IN7
The filter time for two-
channel inputs must
be identical.
The value for the filter time for two-channel
parameterised inputs must be identical.
Correct value and resend the parameter data to the
device.
0x03EX
992dez
1000dez
The least significant four bits
display information on the
affected clock output.
Range of values:
0 Clock output channel UT1
8 Clock output channel UT2
The setting for the
displayed clock output
is outside the
permitted range.
Parameters for the displayed clock output are not
permitted.
Correct value and resend the parameter data to the
device.
0x03F2
1010dez
None
Calculated and
received checksum for
the parameter data
does not coincide.
Check the F_iPar_CRC checksum and resend the
parameter data to the device.
0x03F5
1013dez
None
At least one reserved
bit in the process data
is set.
Reserved bits in the received parameter data may
not be set.
Parameter error in the COMNG_MODE operating mode.
Code
Additional Information
Brief Description
Solution
0x03F7
1015dez
None
Received F address
does not correspond to
the expected value.
The F address received and set on the device does
not coincide.
Additional parameter error in the transfer of the iParameters.
Code
Additional Information
Brief Description
Solution
0x03FB
1019dez
None
Incorrect sequence of
the parameter sets.
iParameters follow F
parameters.
Internal error. Contact SMC if error persists.
0x03FD
1021dez
None
The PST_DEVICE_ID
in the iParameters is
incorrect.
Correct value and resend the parameter data to the
device. Contact SMC for further details

Table of Contents

Related product manuals