MODULYS GP Green Power 2.0 range from 400 to 600 kVA - Ref.: IOMMODGPXX07-EN 00
6. CONTROL PANEL
6-1
LED indicator
Colour Power module Bypass module
Green Module on inverter Bypass ready to start
Flashing green - Load on bypass
Yellow Module ready to start Maintenance bypass
Flashing yellow Module initialising Load on inverter or bypass and transfer impossible/locked
Red Module stopped due to alert Bypass alert present
Flashing red Initialising failure Bypass blocked with alert
Flashing green yellow and red No communication No communication
Control panel luminous status bar indicator
Colour Status
Green Load protected on inverter
Flashing green UPS in startup procedure phase or battery test
Yellow Load supplied with warning (Bypass, maintenance bypass or battery)
Flashing yellow Maintenance request/in progress
Flashing green and yellow Load supplied and preventive alert present
Red Load not supplied: output switched OFF due to an alert
Flashing red Load supplied, but the output will stop in few minutes (imminent stop)
Flashing yellow and red Load supplied, but no more protected
A critical alert has occurred
Flashing green yellow and red No communication
Luminous status bar
Power module LED indicators
Power module LED indicators
Bypass module LED indicator