EasyManua.ls Logo

socomec MODULYS GP - Operation with Maintenance Bypass; Operation with Motor Generator (Genset)

socomec MODULYS GP
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
MODULYS GP Green Power 2.0 range from 400 to 600 kVA - Ref.: IOMMODGPXX07-EN 00
9.4. OPERATION WITH MAINTENANCE BYPASS
If the internal maintenance bypass is activated using the appropriate procedure, the load is powered directly from the maintenance
bypass, while the UPS is separate from the power supply and can be switched off.
This operating mode can be selected for maintenance to be carried out on the system, so that the necessary actions can be perfor-
med by service personnel without having to disconnect the power supply to the load.
9.5. OPERATION WITH MOTOR GENERATOR (GENSET)
The UPS can be operated in conjunction with a generator (GENSET) over the ADC interface (refer to 'Standard features and option'
chapter). With a generator, the frequency and voltage ranges of the auxiliary mains can be increased to accept the instability of the
GE and at the same time to avoid operation from the battery or risks of out-of-synchronisation switching on to the bypass.
9. OPERATING MODES

Other manuals for socomec MODULYS GP

Related product manuals