64
MODULYS GP Green Power 2.0 range from 400 to 600 kVA - Ref.: IOMMODGPXX07-EN 00
12. TECHNICAL SPECIFICATIONS
Model M4-C-400-83-0 M4-C-600-83-0
Power kW 400 600
Power kVA 400 600
Input
Input mains voltage 3ph + N 340 V to 480 V (+20/-15%) up to -40% @ 50% of nominal load
Input mains frequency Hz 50/60 +/-10%
Input power factor ≥ 0.99
(1)
Total harmonic input current distortion (THDi)
≤ 3% (@: Pn, Resistive load, Mains THDv ≤ 1%)
Output
Output voltage (three phase + neutral) V 380/400/415
(2)
selectable
Frequency Hz 50/60 selectable
Total output voltage distortion (THDv) % ≤ 1% (Ph/Ph); ≤ 2% (Ph/N) (@: Pn, Resistive load)
Overload
(3)
% 125% for 10 minutes, 150% for 1 minute
Crest Factor ≥ 2.7
Bypass
Bypass input voltage
V Nominal output voltage ±15% (±20% if GENSET is used)
Bypass input frequency Hz 50/60 +/-2% selectable (±8% if GENSET is used)
Stored energy mode of operation
Number of battery blocks (VRLA) From 18+18 to 24+24
Environmental
Operating temperature °C 0 to 35 °C
(4)(5)
Storage temperature °C -5 to +50 °C
Relative humidity % 95% condensation-free
Altitude (max) m 1000 ( 3000 with derating)
Acoustic noise at 1m dBA 61 64
Required cooling capacity m
3
/h 7300 10500
Dissipated power (max) W 27500 39500
Dissipated power (max) BTU/h 93870 134800
Dimensions and Weight
Coupling Dimensions (W x D x H) mm 810 x 890 x 1975
Coupling kg 327
Unit Dimensions (W x D x H) mm 600 x 890 x 1975
Unit empty cabinet kg 228
UPS module kg 33
Bypass module kg 25
Standard
Safety IEC 62040-1
EMC IEC 62040-2 (C2)
Performance IEC 62040-3 (VFI-SS-111)
Product Certifications CE
Degree of protection standard IP20
(1). Pout ≥ 50% Sn.
(2). 360 V with Pout = 90% Pn.
(3). Initial Condition Pout ≤ 80% Pn
(4). For best battery lifetime the suggested temperature range is 15 °C ÷ 25 °C.
(5). According to EN62040-3