MODULYS GP Green Power 2.0 range from 400 to 600 kVA - Ref.: IOMMODGPXX07-EN 00
8.4. EXTENDED OUT OF SERVICE
When the UPS is deactivated for some time, the batteries must be recharged regularly.
They have to be recharged every three months.
• Check output switch Q70 (output load) into position 0.
• Connect the input and auxiliary mains to the coupling (A and B).
• Wait until the displays switch on.
• Close the external battery breaker/fuses.
• Wait until the batteries are fully charged. Check in the menu MAIN MENU > MEASUREMENT > BATTERIES MEASUREMENT.
• Open the external battery breaker/fuses.
• Disconnect the input and auxiliary mains to the coupling (A and B).
8.5. EMERGENCY SHUTDOWN
NOTE!
This operation interrupts the supply to the output load from both inverters and automatic bypass.
UPS POWER OFF
Put the switches Q70 and Q80 at position 0 (located on the coupling cabinet).
REMOTE UPS POWER OFF
If an external main switch is present, it is possible to interrupt the power supply to the output load using the ADC board. Refer to
‘Standard features and options’ chapter.
8. OPERATING PROCEDURES
Q70-OFF
Q70
Q80-OFF
Q80
8.5-1

Other manuals for socomec MODULYS GP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec MODULYS GP and is the answer not in the manual?

socomec MODULYS GP Specifications

General IconGeneral
TopologyDouble Conversion Online
Frequency50/60 Hz
EfficiencyUp to 96%
ModularYes
Input Voltage400 V
Output Voltage400 V
Battery TypeVRLA
Communication PortsRS232, USB, SNMP
Operating Temperature0 to +40 °C
HumidityUp to 95 % non-condensing

Related product manuals