8 Troubleshooting handling
8.1 Troubleshooting
This section contains information and procedures pertaining to
the remedying of potential problems with the inverter.
To carry out troubleshooting, proceed as follows:
Check the warnings, error messages or error codes displayed
on the screen of the inverter.
If no error information is displayed on the screen, check whether
the following requirements have been fulfilled:
Has the inverter been set up in a clean, dry, well-ventilated
area?
Is the DC switch set to ON?
Are the cables sufficiently dimensioned and short enough?
Are the input connections, output connections and the
wiring all in good condition?
Are the configuration settings for the relevant installation
correct?
Are the display field and the communication cables
correctly connected and undamaged?
Follow the steps below to view recorded problems: Press “Back”
to enter the main menu in the normal interface. In the interface
screen select "Event List", then press “OK” to enter events.
8.1.1 Shutdown procedure
If the inverter needs to be shut down for electrical inspection,
please follow the following steps:
1. Press the "Back" on the main interface to enter the main
menu page, and select Advanced Settings - Switch On/Off -
Switch Off. Make the inverter shut down safely.
2. Note: after using the menu setting to shut down the
inverter, the inverter should be checked and reenergising, it
still needs to be on the main menu page. Select advanced