HYD 5/6/8/10/15/20KTL-3PH USER MANUAL
Table. 5-20 Logic interface description(d)
5.11 Feed-in limit function
The feed-in limit function can be used to limit the power fed
back into the grid. For this function, a power measurement
device must be installed according to system A, B, or C.
Feed-in limit: The sum of the feeding-in phases must not
exceed the set power limitation value. The power of phases
drawing power from the grid is disregarded here.
3-phase limit: The sum of the feed-in power of all three phases
must not exceed the set power limit value. This setting is
suitable for balancing metering, as is common in Germany, for
example.
For the 3-phase limit setting, the current sensors
must be correctly assigned to phases L1, L2 and L3 on
the electricity meter!
If communication with the smart meter is interrupted,
the inverter limits its output power to the set power
limit value.
5.12 System monitoring
The HYD 5/6/8/10/15/20KTL-3PH inverters provide various
communication methods for the system monitoring:
RS485 or WiFi stick (standard), or Ethernet stick (optional).