EasyManua.ls Logo

Sonel PAT-1 - Page 27

Sonel PAT-1
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OPERATING MANUAL PAT-1, PAT-2, PAT-2E, PAT-10 version 1.02
25
or
Press
ENTER
to confirm settings or
press ESC to exit without saving
the changes.
Press START/STOP to commence
measurement of PE protective conductor
resistance.
Correct result. The value
of insulation resistance is
above the set limit. Green
LEDs of PASS indication
are on.
Connect test leads according to the drawing :
For Class I appliances, the previous R
PE
test has to have positive result. The
measurement is made between shorted L, N and PE. Connection diagram for
Class I appliances (there is possibility, in most cases not required, to carry out the
measurement with the test lead with probe connected to T
2
terminal socket):
Connection diagram for Class II (III) appliances. The test lead with the probe
must be connected to T
2
terminal socket. The measurement is made between
shorted L and N, and the probe:

Table of Contents