13
IM-S51-07 CTLS Issue 1
SP7-10, SP7-11, SP7-12 and SP7-20, SP7-21, SP7-22 Parameterization
3.3 4.20mA and 4-20mA HART parameter descriptions (SP7-10 and SP7-20)
Parameter Display Function
Possible parameter
setting
Unit
Factory
setting
P1._ STANDARD Actuator type Actuator type LINEAR, ROTARY - - - LINEAR
P1.0 ACTUATOR Auto adjust Autoadjust Function --- ---
P1.1 AUTO ADJ Auto adjust mode
Automatic
adjustment mode
FULL,STROKE,CTRL_PAR,
ZERO_POS, LOCKED
FULL
P1.2 ADJ_MODE
P1.3 TEST Test Test Function --- INACTIVE
P1.4 FIND_DEV Find device Find device
DISABLE, ONE TIME,
CONTINOUS --- DISABLED
P1.5 EXIT Return
Return to
operating level
Function --- NV SAVE
P2._ SETPOINT
P2.0 MIN_RGE Min setpoint range
Min. setpoint
range
4.0 ... 18.4 mA 4.0
P2.1 MAX_RGE
Max setpoint
range
Max. setpoint
range
20.0 ... 5.6 mA 20.0
P2.2 CHARACT Ch aract. curve
Characteristic
curve
LINEAR, 1 :25, 1 50, 25 1, 50 1,
USERD
--- LINEAR
P2.3 ACTION Valve action Effective direction DIRECT, REVERSE --- DIRECT
P2.4 SHUT_CLS Shut-off value 0% Shut-off value O % OFF, 0.1 ... 45.0 % 1.0
P2.5 SHUT_OPN
Shut off value
100%
Shut-off value 100
%
55.0 ... 100.0, OFF % OFF
P2.6 RAMP UP Set point ramp, up Setpoint ramp (up) OFF, 0 ... 200 --- OFF
P2.7 RAMP DN
Set point ramp,
down
Setpoint ramp
(down)
OFF, 0 ... 200 --- OFF
P2.8 EXIT
P3._ ACTUATOR
P3.0 MIN_RGE Return
Return to
operating level
Function --- NV SAVE
P3.1 MAX_RGE
Min. of stroke
range
Operating range,
min.
0.0 ... 90.0 % 0.0
P3.2 ZERO_POS
Max. of stroke
range
Operating range,
max.
100.0 ... 10.0 % 100
P3.3 EXIT Zero position Zero position CLOCKWISE, CTCLOCKWISE --- CTCLOCKWISE