IM-S51-07 CTLS Issue 1
58
SP7-10, SP7-11, SP7-12 and SP7-20, SP7-21, SP7-22 Parameterization
4.1a Error codes (continued)
Error code Possible cause Impact
Troubleshooting the
Instrument
Error while processing the
measured values, pointing to
an error in the working data
(RAM).
The actuator is moved to the
safe position. After approx. 5
seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
Error during the table
processing, pointing to an
error in the working data
(RAM).
The actuator is moved to the
safe position. After approx. 5
seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
Error when verifying the
checksum of the configuration
data (RAM).
The actuator is moved to the
safe position. After approx. 5
seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
Error in the processor
function registers (RAM).
The actuator is moved to the
safe position. After approx. 5
seconds, the positioner is
automatically reset and the
RAM is reinitialized.
If the error persists even after
the positioner has been reset,
the device will need to be
returned to the manufacturer
for repair.
Internal error.
The actuator is moved to the
safe position. After approx. 5
seconds, the positioner is
automatically reset.
If the error can be reproduced
and occurs in the same
position after resetting, the
device must be returned for
repair to the manufacturer.