EasyManua.ls Logo

Square QED-2 - Water-Sprayed or Splashed Switchboards (Clean Water Only); Inspection and Clean-Up of Clean Water Sprayed or Splashed Switchboards

Square QED-2
188 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 8—Adverse Circumstances Power-Style™ QED-2 Switchboards
49© 1988–2018 Schneider Electric All Rights Reserved80043-055-13
ENGLISH
Water-Sprayed or Splashed Switchboards (Clean Water Only)
If the switchboard has been sprayed or splashed with small amounts of clean
water, make a thorough inspection of the entire system, and verify that no damage
to conductors or insulation has occurred. Do not open sealed devices such as
molded case circuit breakers or fuses. Replace these devices if they are damaged.
For more information about these devices, refer to the appropriate instruction
manual listed in “Section 11—Reference Publications”.
Inspection and Clean-up of
Clean Water Sprayed or
Splashed Switchboards
Follow steps 1–10 only if:
No signs of physical damage to the equipment are present.
The switchboard has not been submerged or exposed to water for long periods
of time.
The water that has been in contact with the switchboard has not been
contaminated with sewage, chemicals, or other substances that can negatively
affect the integrity of the electrical equipment.
The water that has been in contact with the switchboard has not entered any
area of the enclosure that may contain wiring installed as intended and located
above any live part. Specifically, inspect for water entering through conduits
located above live parts.
If any one or more of these conditions have not been met, contact
Schneider Electric Services at 1-888-778-2733 (US) or 1-800-565-6699 (Canada).
If ALL of the conditions listed have been met, proceed as follows:
1. Turn off all power supplying this equipment before working on or inside
the equipment.
2. Always use a properly rated voltage sensing device to confirm all power is off.
3. Disconnect and electrically isolate the switchboard so that no contact can be
made with energized parts.
4. Wipe off all moisture from the bus bars, insulators, and insulating material
with a clean, dry, lint-free cloth. Do not use cleaning agents or water
displacement sprays.
5. Prepare the switchboard for insulation resistance (Megger
®
) testing by
disconnecting all line side supply connections and all load side cable
connections to isolate the switchboard from the wiring system.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Turn off all power supplying this equipment before working on it.
Failure to follow these instructions will result in death or serious injury.

Table of Contents