Start-up STULZUltraSonic-SystemforDirectRoomHumidicationBNB-
Proceedasfollowstoensuresafestart-up:
2
Switch on the controller/electrical supply of the
ultrasonichumidier.
1
Establish a supply of demineralized drinking
water:
a)Opentheon-sitestopcockinthedrinking
water supply pipe.
b)Checkthedemineralizeddrinkingwater
attheultrasonichumidier.
3
Set the parameters of the humidity controller to
achieve the desired air humidity.
4
Checkthefunctionofthehumidier:
a)Ismistemittedfromallmistoutlets?
b)Arepush-inandscrewconnectionstight?
c)Isthemistdistributedevenlyandis
there no possibility of condensation?
5
Ifyouhavemadesurethehumidierisfunction-
ing correctly, start-up is complete.
Otherwise, proceed with step 6.
After successful start-up, clean the unit
"11.4. Cleaning" on page 76.
CAUTION
Humidier start-up.
Thehumidierbeginstohumidifytheroomwhenthewatertankintheunitisfull.
●
This may take a few minutes.
Note
CAUTION
Initial start-up.
Thersttimethehumidierisused,impuritiesmayoccurifnotallaffectedparts
of the pipeline system have been cleaned before installation.
Note
CAUTION
Uneven mist expulsion.
If mist is expelled unevenly, check that the unit is positioned horizontally.
Note
CAUTION
Pay attention to controller.
Before start-up, read the technical guide of the controller you are using.