EasyManua.ls Logo

Subaru impreza 2017 - Door Locks; Locking and Unlocking from the Outside

Subaru impreza 2017
786 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
X
a
a>b
b
IN>Dir
polMethod=Voltage
polMethod=Dual
OR
FORWARD_Int
REVERSE_Int
BLOCK
STAGE1_DIR_Int
0.6
X
0.4
AND
STAGE3_DIR_Int
STAGE4_DIR_Int
STAGE2_DIR_Int
OR
STRV
UPolMin
IPolMin
AngleRCA
T
F
0.0
X
T
F
RNPol
XNPol
0.0
Directional
Characteristic
FWD
RVS
AND
AND
AND
STFW
FORWARD_Int
REVERSE_Int
AND
IEC07000067-6-en.vsdx
|
|
UPol
UIPol
IPol
I3PDIR
UTotPol
IopDir
Complex
Number
a
a>b
b
T
F
0.0
polMethod=Current
OR
IEC07000067 V6 EN-US
Figure 45: Simplified logic diagram for directional supervision element with integrated directional
comparison step
6.4.7.9 Second harmonic blocking element
M13941-200 v8
A harmonic restrain can be chosen for each step by a parameter setting
HarmBlockx. If the ratio of the 2nd harmonic component in relation to the
fundamental frequency component in the residual current exceeds the preset level
(defined by parameter 2ndHarmStab), output signal 2NDHARMD is set to logical
value one and the harmonic restraining feature to the function block will be
applicable.
Blocking from the 2nd harmonic element activates if all of three criteria are
satisfied:
1. The fundamental frequency component of the current > 1% of IBase
2. The second harmonic component > 1% of IBase
3. The ratio of the 2nd harmonic component in relation to the fundamental
frequency component in the residual current exceeds the preset level defined
by the parameter 2ndHarmStab setting
1MRK 505 384-UEN A Section 6
Current protection
Breaker protection REQ650 2.2 IEC 121
Technical manual

Table of Contents