Name Values (Range) Unit Step Default Description
U2AngDbRepInt 1 - 100000 s 1 10 Cyclic report interval (s)
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 5% of Ur
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 30% of Ur
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage
at 100% of Ur
Table 311: VMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3U0HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
3U0HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
3U0LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
3U0LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U1HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U1HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U1LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U1LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U2HiHiLim 0.0 - 200.0 %UB 0.1 150.0 High High limit in % of UBase
U2HiLim 0.0 - 200.0 %UB 0.1 120.0 High limit in % of UBase
U2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
PID-6737-SETTINGS v2
Table 312: VNMMXU Non group settings (basic)
Name
Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 100000 Type 1 10 Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
Operation Off
On
- - Off Operation Mode On / Off
UL1ZeroDb 0 - 100000 m% 500 1000 Magnitude zero point clamping in
0,001% of range
UL1Min 0.0 - 200.0 %UB 0.1 50.0 Minimum value in % of UBase
UL1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
UL1RepTyp Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
- Cyclic Reporting type
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range, common
for all limits
Table continues on next page
Section 11 1MRK 505 384-UEN A
Monitoring
408 Breaker protection REQ650 2.2 IEC
Technical manual