10.7.9.3 Settings
PID-6976-SETTINGS v1
Table 254: TIMERSET Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
10.7.9.4 Technical data
GUID-C6C98FE0-F559-45EE-B853-464516775417 v2
Table 255: Number of TIMERSET instances
Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSET 15 15 30 (0.000–90000.000) s ±0.5% ±10 ms
10.7.10 Exclusive OR function block XOR
IP11018-1 v2
M11477-3 v4
The exclusive OR function (XOR) is used to generate combinatory expressions
with boolean variables. XOR has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they
are the same.
Table 256: Truth table for XOR function block
INPUT1
INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1
10.7.10.1 Function block
M11476-3 v1
IEC04000409-2-en.vsd
XOR
INPUT1
INPUT2
OUT
NOUT
IEC04000409 V2 EN-US
Figure 179: XOR function block
Section 10 1MRK 505 384-UEN A
Logic
364 Breaker protection REQ650 2.2 IEC
Technical manual