Name Type Default Description
EEH_WARN BOOLEAN 0 Warning from external equipment
EEH_ALM BOOLEAN 0 Alarm from external equipment
XIN GROUP
SIGNAL
- Execution information from CSWI
PID-6800-OUTPUTSIGNALS v3
Table 173: SXSWI Output signals
Name Type Description
XPOS GROUP SIGNAL Group connection to CSWI for XCBR and XSWI
EXE_OP BOOLEAN Executes the command for open direction
EXE_CL BOOLEAN Executes the command for close direction
OP_BLKD BOOLEAN Indication that the function is blocked for open
commands
CL_BLKD BOOLEAN Indication that the function is blocked for close
commands
UPD_BLKD BOOLEAN Update of position indication is blocked
OPENPOS BOOLEAN Apparatus open position
CLOSEPOS BOOLEAN Apparatus closed position
CNT_VAL INTEGER Operation counter value
L_CAUSE INTEGER Latest value of the error indication during
command
EEHEALTH INTEGER External equipment health. 1=No warning or
alarm, 2=Warning, 3=Alarm
SWOPCAP INTEGER Switch operating capability 1 = None, 2 = O, 3 =
C, 4 = O and C
9.4.8.4 Settings
PID-6800-SETTINGS v3
Table 174: SXSWI Non group settings (basic)
Name
Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to
move after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end
position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break
Disconnector
Earthing Switch
HS Earthing Switch
-
- Disconnector 1=LoadBreak,2=Disconnector,
3=EarthSw,4=HighSpeedEarthSw
InitialCount 0 - 20000 - 1 0 Initial number of operations (Initial count
value)
Section 9 1MRK 505 384-UEN A
Control
298 Breaker protection REQ650 2.2 IEC
Technical manual