6.9.4 Signals
PID-3479-INPUTSIGNALS v6
Table 93: BRCPTOC Input signals
Name
Type Default Description
I3P GROUP
SIGNAL
- Group signal for current input
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
PID-3479-OUTPUTSIGNALS v7
Table 94: BRCPTOC Output signals
Name Type Description
TRIP BOOLEAN Operate signal of the protection logic
START BOOLEAN Start signal of the protection logic
6.9.5 Settings
PID-3479-SETTINGS v7
Table 95: BRCPTOC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
Iub> 50 - 90 %IM 1 50 Highest and lowest phase currents
difference in % of highest phase current
IP> 5 - 100 %IB 1 20 Minimum phase current for operation of
Iub> in % of IBase
tOper 0.000 - 60.000 s 0.001 5.000 Operate time delay
Table 96: BRCPTOC Group settings (advanced)
Name
Values (Range) Unit Step Default Description
tReset 0.010 - 60.000 s 0.001 0.100 Time delay in reset
Table 97: BRCPTOC Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
1MRK 505 384-UEN A Section 6
Current protection
Breaker protection REQ650 2.2 IEC 159
Technical manual