execute command
position L1
t1>tExecutionFB, then
long-operation-time in
'cause' is set
open
close
close
openposition L3
close
openposition L2
t1
tExecutionFB timer
cmd termination L1
cmd termination L2
cmd termination L3
cmd termination
position
open
close
* The cmd termination will be delayed one execution sample.
*
APCtExecutionFB=IEC0
5000094=2=en=Original
.vsd
IEC05000094 V2 EN-US
Figure 132: tExecutionFB
The parameter tSynchrocheck is used to define the maximum allowed time between
the execute command and the input SYNC_OK to become true. If SYNC_OK=true
at the time the execute command signal is received, the timer "tSynchrocheck" will
not start. The start signal for the synchronizing is obtained if the synchrocheck
conditions are not fulfilled.
The parameter tSynchronizing is used to define the maximum allowed time
between the start signal for synchronizing and the confirmation that synchronizing
is in progress.
Section 9 1MRK 505 384-UEN A
Control
288 Breaker protection REQ650 2.2 IEC
Technical manual