EasyManua.ls Logo

Subaru impreza 2017 - Page 99

Subaru impreza 2017
786 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer
programmable curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer
programmable curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer
programmable curve for step 4
HarmBlock4 Off
On
- - Off Enable block of step 4 from harmonic
restrain
Table 42: OC4PTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
MeasType DFT
RMS
- - DFT Selection between DFT and RMS
measurement
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base
Value groups
6.2.6 Monitored data
PID-6973-MONITOREDDATA v3
Table 43: OC4PTOC Monitored data
Name
Type Values (Range) Unit Description
DIRL1 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase1
DIRL2 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase2
DIRL3 INTEGER 1=Forward
2=Reverse
0=No direction
-
Direction for phase3
IL1 REAL - A Current in phase L1
IL2 REAL - A Current in phase L2
IL3 REAL - A Current in phase L3
6.2.7 Operation principle
M12883-3 v10
Directional phase overcurrent protection, four steps OC4PTOC is divided into four
different sub-functions. For each step x , where x is step 1, 2, 3 and 4, an operation
mode is set by DirModex: Off/Non-directional/Forward/Reverse.
The protection design can be divided into four parts:
1MRK 505 384-UEN A Section 6
Current protection
Breaker protection REQ650 2.2 IEC 93
Technical manual

Table of Contents

Other manuals for Subaru impreza 2017

Related product manuals