96 Sun Fire V880 Server Rackmounting Guide May 2004
Airflow For proper ventilation of the server, the front and rear doors of the
Sun Rack 900 cabinet comply with the following minimum open
area requirements.
60 percent of the area of the front door that is directly in front
of the server is open.
63 percent of the area of the rear door that is directly behind the
server is open.
The doors of the Sun Rack 900 cabinet meet the open area
requirements of the Sun Fire V890 server.
Vertical Mounting Rails The Sun Rack 900 cabinet has two pairs of vertical mounting rails
(one pair in front, one in back) that conform to the EIA (RETMA)
standard for mounting hole spacing.
Front-to-rear rail spacing of the Sun Rack 900 cabinet is
27 inches (68.58 cm) from the outside face of the front rail to the
outside face of the rear rail.
Front and rear vertical rail mounting faces of the Sun Rack 900
cabinet are parallel to each other and to the front plane of the
cabinet.
EMI Electromagnetic interference (EMI) shielding requirements are
met by the system chassis and metal side doors, which must
remain in place when the unit is installed in the cabinet.
Fire Containment The Sun Rack 900 cabinet meets Underwriters Laboratories, Inc.
and TUV Rheinland of N.A. requirements for fire containment.
Cabinet Feature Requirement

Table of Contents

Other manuals for Sun Microsystems Sun Fire V890

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sun Microsystems Sun Fire V890 and is the answer not in the manual?

Sun Microsystems Sun Fire V890 Specifications

General IconGeneral
BrandSun Microsystems
ModelSun Fire V890
CategoryServer
LanguageEnglish

Related product manuals