EasyManua.ls Logo

Sungrow 1000A - Connection to Energy Meter; Connection to Meteo Station

Sungrow 1000A
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical Connection User Manual
24
Different device types must connect to different RS485 communication ports of
the Logger1000. For example, connect the transformer and inverter to different
RS485 communication ports of the Logger1000.
The addresses of devices on each RS485 bus must be different from one another
and within the address range set for the Logger1000 (address range of residential
inverters and string inverters manufactured by SUNGROW: 1-247; address range
of third-party devices: 1-255). Otherwise, communication error will occur.
Serial port parameters of each device on the RS485 bus should be consistent
with those of the Logger1000. The serial port parameters include baud rate, data
bit, stop bit, and check bit.
6.3.2 Connection to Energy Meter
It is recommended to use the energy meter whose communication protocol
complies with DL/T645-2007 protocol or Modbus RTU protocol. The recommended
energy meter types are as follows:
No.
Manufacture
Type
1
Sfere
PD194E/Z
2
Acrel
PZ96-E3
3
Acrel
DTSD1352
4
Janitza
UMG604
The following figure shows the connection between the Logger1000 and the energy
meter.
Logger1000
Energy meter
Connect the communication cable led from the energy meter to the RS485 port of
the Logger1000.
All devices on each RS485 bus support the same communication
protocol.
6.3.3 Connection to Meteo Station
The following figure shows the connection between the Logger1000 and the Meteo
Station.

Table of Contents

Related product manuals