6 Control Method
6.1 Plant Lumped Parameter
step 1 Click CCoonnttrrooll MMeetthhooddPPllaanntt LLuummppeedd PPaarraammeetteerr to enter the corresponding interface.
The figure is for reference only. The actual interface may be different and shall
prevail.
step 2 Click
to set the local/remote, dispatch interruption control method, priority, and
debug mode switch parameters.
PPaarraammeetteerr
DDeessccrriippttiioonn
LLooccaall//RReemmoottee
Local
Enable the local mode when no need
to receive AGC or AVC dispatch
instructions
Remote
Enable the remote mode when need to
receive AGC and AVC dispatch
instructions
DDiissppaattcchh
iinntteerrrruuppttiioonn
ccoonnttrrooll mmooddee
Keep current value
Keep the current value when
communication is interrupted
Zero power output
Issue the zero power output instruction
when communication is interrupted