11
PPaarraammeetteerr
DDeessccrriippttiioonn
PPrriioorriittyy
Reactive priority
Give priority to reactive power output
within the range of apparent power
limit
Active priority
Give priority to active power output
within the range of apparent power
limit
DDeebbuugg mmooddee
sswwiittcchh
Enable
Enable debug mode, and the power
distribution and slope control are
disabled. Power control instructions
will not be sent to the PCS or PV
inverters.
Disable
Disable debug mode
RRaatteedd ccaappaacciittyy ooff
eenneerrggyy ssttoorraaggee
((MMWWhh))
Default value 0.100
Set the value according to actual
situation
step 3 Click DDiissppaattcchh BBaacckk--eenndd CCoonnffiigguurraattiioonn, enter the DDiissppaattcchh BBaacckk--eenndd CCoonnffiigguurraattiioonn
interface, set the DDiissppaattcchh IInntteerrrruuppttiioonn CCoonnttrrooll SSwwiittcchh status, and click CCoonnffiirrmm.
If DDiissppaattcchh IInntteerrrruuppttiioonn CCoonnttrrooll SSwwiittcchh is set to EEnnaabbllee, it is required to
enter the IP address of the dispatch background, and at most 2 IP addresses
can be entered.
step 4 Click SSaavvee.
-- -- EEnndd
6.2 Primary Frequency Modulation
This function can realize real-time grid-connected point frequency detection and
automatic control to keep the frequency within the safe range.
step 1 Click CCoonnttrrooll MMeetthhooddPPrriimmaarryy FFrreeqquueennccyy MMoodduullaattiioonn to enter the corresponding
interface.
step 2 Click
to set the status of FFuunnccttiioonn CCoommmmiissssiioonniinngg//CCeeaassiinngg and "SSeeggmmeenntt
NNuummbbeerr, Click SSaavvee.
User Manual 6 Control Method