8.6 Transfer Configuration
8.6.1 IEC104
Configure the IEC104 forwarding service for the controller on this interface.
Click SSyysstteemm→→TTrraannssffeerr CCoonnffiigguurraattiioonn→→IIEECC110044 to enter the corresponding interface.
The local port is 2404.
GGeenneerraattee PPooiinntt TTaabbllee
Turn on the switch of local port 2404.
Click GGeenneerraattee PPooiinntt TTaabbllee, and default IEC104 point table will be automatically
imported to configuration file.
EExxppoorrtt PPooiinntt TTaabbllee
Click EExxppoorrtt PPooiinntt TTaabbllee to download the point list to the local.
WWhhiittee LLiisstt SSeettttiinngg
Click WWhhiittee LLiisstt SSeettttiinngg to enter the interface.
When the option EEnnaabbllee WWhhiittee LLiisstt is not selected, and the peer IP address is "0.0.0.0",
any background devices with valid IP address can access the controller.
When the option EEnnaabbllee WWhhiittee LLiisstt is selected, and peer IP address is entered, only the
device with the specified IP address can access the controller.
AAddvvaanncceedd SSeettttiinnggss
Click
on the operation bar to enter the AAddvvaanncceedd SSeettttiinnggss interface. Set the
remote signaling measuring point type, remote signaling time mark, and upload with a
change.
Click the button
on the pop-up window, to import the xml file.
Click SSaavvee.
EExxppoorrtt IIEECC110044 FFoorrwwaarrddiinngg PPooiinntt TTaabbllee
Click
to export the forwarding point table in .xml or .csv format to local.
8.6.2 MODBUS
Configure the MODBUS forwarding service for the controller on this interface.
Click SSyysstteemm→→TTrraannssffeerr CCoonnffiigguurraattiioonn→→MMOODDBBUUSSto enter the corresponding
interface.
Refer to " White List Setting"for white list setting.
8.6.3 GOOSE
Configure the GOOSE forwarding service for the controller on this interface.
step 1 Click SSyysstteemm→→TTrraannssffeerr CCoonnffiigguurraattiioonn→→GGOOOOSSEE to enter the "GOOSE" interface.