16
The figure is for reference only. The actual interface may be different and shall
prevail.
PPaarraammeetteerrss
DDeessccrriippttiioonn
FFuunnccttiioonn
CCoommmmiissssiioonnii--
nngg//CCeeaassiinngg
Commissioning
Set a fixed value for active power
control
Ceasing
—
LLooccaall//RReemmoottee
Local
Set Value
(MW)
Set a fixed value locally for
control
Remote
Receive the fixed value issued by
AGC for active power control
CCoonnttrrooll DDeeaadd
ZZoonnee ((kkWW))
Default value 0.010
Set the value according to actual
situation
When setting the llooccaall//rreemmoottee status, it must be consistent with the llooccaall//
rreemmoottee status of the plant lumped parameter, otherwise the policy will not be
executed.
step 3 Click SSaavvee to complete the setting of the fixed value parameters for the active power
control.
-- -- EEnndd
6.4.2 Planning Curve
Active power curve control: Control the plant to output active power according to the
power curve.
FFuunnccttiioonn CCoommmmiissssiioonniinngg//CCeeaassiinngg on the PPllaannnniinngg CCuurrvvee and the FFiixxeedd
VVaalluuee interfaces can not be set toCCoommmmiissssiioonniinngg at the same time.
step 1 Click CCoonnttrrooll MMeetthhoodd→→AAccttiivvee PPoowweerr CCoonnttrrooll→→PPllaannnniinngg CCuurrvvee to enter the
corresponding interface.
step 2 Click
to set the status of the FFuunnccttiioonn CCoommmmiissssiioonniinngg//CCeeaassiinngg, LLooccaall//RReemmoottee
and to set the parameter values for CCoonnttrrooll DDeeaadd ZZoonnee.
6 Control Method User Manual