table 6-2 Cable Specification of Multi-branch Version
Cable
Specifications
Connec-
tion holes
Requ.
Note
DC input
The cross-sectional area of the
positive and negative input ca-
bles is 240 mm
2
(or 600 kcmil)
at most
Each
branch
has two
wiring
holes.
Φ13
Alumi-
num/Cop-
per ca-
bles can
be flexi-
bly se-
lected to
bear the
max
current.
AC output
The cross-sectional area of
each phase inputs is 240 mm
2
(or 600 kcmil)at most (PCS
stand-alone AC output side)
Six inputs,
each with
two holes
arranged
up and
down for
each
phase
wiring.
Φ13
Alumi-
num/Cop-
per ca-
bles can
be flexi-
bly se-
lected to
bear the
max
current.
RS485 com-
munication
cable
2-core twisted shielded pair
cable
- - -
Can communi-
cation cable
0.75 mm
2
- - -
Network cable Standard network cable
- - -
AC side
It is recommended to connect the AC side to the low voltage side of the downstream
transformer directly through the copper bar.
Ground connection
There are ground connection points on the container base.
It is recommended to use copper wire cable with specification of at least 100Kcmil.
External communication
System Manual 6 Electrical Connection

Table of Contents

Other manuals for Sungrow SC3150UD-MV-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SC3150UD-MV-US and is the answer not in the manual?

Sungrow SC3150UD-MV-US Specifications

General IconGeneral
BrandSungrow
ModelSC3150UD-MV-US
CategoryStorage
LanguageEnglish

Related product manuals