GB.GOLDSK509.091101
We reserve the right to alter specifications without notice.
www.swegon.com 77
Alarm No.:
Function
Factory preset values Adjusted value
Priority Indication Effect Priority Indication Effect
0=blocked LED 0=Operat. 0=blocked LED 0=Operat.
A=A alarm 0=Off 1=Stop A=A alarm 0=Off 1=Stop
B=B alarm 1=On B=B alarm 1=On
86 CoolDX, C2 tripped A 1 0
87 CoolDX, C1 too many restarts A**** ! 1
88 CoolDX, C2 too many restarts A**** 1 1
89 No comm. with press. sensor by SA prefilter B*** 1 0
90 No comm. with press. sensor by EA prefilter B*** 1 0
91 Frost prot. for preheating, below alarm limit A 1 1
92 Frost prot. for preheating sensor, faulty A 1 1
93 Preheating sensor faulty A 1 1
94 Electric air heater for preheating, tripped A*** 1 1
95 Preheating below setpoint A*** 1 1
97 No comm. with ReCO2 pressure sensor A*** 1 1
98 ReCO2 damper motor faulty A*** 1 1
99 Time lock tripped A 1 1
102 Cooling valve I/O-7 defective B*** 1 0
103 Heating valve I/O-7 defective A*** 1 0
104 Cool. circuit pump I/O-7 tripped B*** 1 0
105 Heat. circuit pump I/O-7 tripped A*** 1 1
106 Cooling water temp. I/O-7 below set point B*** 1 0
107 Heat. water temp. l I/O-7 below set point A*** 1 0
108 Cooling water temp. I/O-7 above set point 0*** 1 0
109 Heating water temp. I/O-7 above set point 0*** 1 0
110 Cooling water temp. sensor I/0-7 defective B 1 0
111 Heating water temp. sensor I/0-7 defective A 1 0
135
SA fan motor blocked
A*** 1 1
136
EA fan motor blocked
A*** 1 1
137
SA-2 fan motor blocked
A*** 1 1
138
EA-2 fan motor blocked
A*** 1 1
139
Fluctuation voltage between the phases, SA
A*** 1 1
140
Fluctuation voltage between phases, EA
A*** 1 1
141
Fluctuation voltage between the phases, SA-2
A*** 1 1
142
Fluctuation voltage between phases, EA-2
A*** 1 1
143 No communication - CONTROL Optimize B*** 1 0
144 No communication – I/O Module No. A B*** 1 0
145 No communication – I/O Module No. B B*** 1 0
146 No communication – I/O Module No. C B*** 1 0
147 No communication – I/O Module No. D B*** 1 0
148 No communication – I/O Module No. E B*** 1 0
149 No communication – I/O Module No. F B*** 1 0
150 Frost prot. in extra zone, below alarm limit A 1 1
151 Frost protection sensor in extra zone, faulty A 1 1