4-11
4
Mounting and Connection
B 165 B
8056
A 140 70
A
B 165 B
8056
A 140 70
A
Terminal cover
Arc Space ()
Arc Space ()
Terminal cover
Terminal cover
Terminal cover
Insulating plate
(supplied as standard)
Insulating plate
(supplied as standard)
Mounting plate
Mounting plate
Insulating plate
(Front)
(Not included item)
Insulating plate
(Rear)
Insulating plate
(Front)
(Not included item)
Insulating plate
(Rear)
Mounting plate
Mounting plate
PVS160-GDH 4P, PVS250-GDH 4P
Front-connected
Rear-connected
Type Connection
PVS160-GDH 4P
PVS250-GDH 4P
Front-connected
Rear-connected
50
Minimum insulation distance (mm) Insulating plate
A B
Terminal cover
80
2pcs are supplied for
line and load side as
standard.
Insulating plate
2pcs of 240mm×162.5mm
are supplied as standard.
Terminal cover lock
2pcs are supplied for
line and load side as
standard.
Arc space is the same dimension as the insulation plate (rear).