4 Operation
37
4.8.2 Alarm settings
4.8.2.1 Creating and displaying alarm settings
Click on the "+ New alarm setting” button.
New alarm setting can be set.
Existing alarm settings are displayed below the button.
- Click on the title of an alarm setting.
An existing setting is displayed.
4.8.2.2 Configuring and editing a displayed alarm setting
The following settings can be defined and edited.
Setting Description
Title Designation of the alarm setting
Measuring points Measuring point group/measuring
point which is to be monitored. Click
on the checkbox in front of the
measuring point group/measuring
Alarm thresholds 1 and 2 Different limit value ranges which can
be defined for different periods.
Values which are to be monitored
Alarm delay Minimum duration of a limit value
violation before an alarm is triggered.
The time intervals between
measurements (measuring cycle)
should be lower than the alarm delay
(e.g. measuring cycle = 5 minutes,
alarm delay = 15 minutes).