TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 9 06/04/24 Thomson Technology
41
NOTE:
Phase balance feature is provided in TSC 800 Software version
2.0 (or higher).
7. PROGRAMMING INSTRUCTIONS
7.1. PASSWORDS
Access to the programmable parameters of the TSC 800 Transfer Controller is via a security
password number. Three levels of security passwords are provided as described below:
7.1.1. READ ONLY MODE
User can view the programmable parameters only and cannot change any values.
The Factory default number for the read-only mode is one (1).
7.1.2. READ / WRITE MODE
User can view and modify any programming parameter as required. The Factory
default number for the read/write mode is two (2).
7.1.3. MASTER READ / WRITE MODE
User can view/modify any programming parameter as well as view/modify the security
password level numbers. Consult THOMSON TECHNOLOGY factory for master
password number if required.
To enter the programming mode, follow the procedure as shown:
Program Menu
Yes
Select the Program Menu by scrolling through the display screens using the ENTER or
EXIT pushbuttons. When displayed, use the INCREMENT pushbutton to select the
YES prompt and push the ENTER button.
Password
0
Use the INCREMENT or DECREMENT pushbuttons to ramp the displayed number up
or down to the desired password access number. Press the ENTER pushbutton when
the correct number is displayed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.1 and is the answer not in the manual?

THOMSON TSC 800 - V2.1 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.1
CategoryController
LanguageEnglish

Related product manuals