TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 9 06/04/24 Thomson Technology
46
7.3.5. TRANSFER FAIL CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when the transfer switch fails to operate. The
callout signal will only reset when the “Fail to Transfer” alarm is manually
reset via local pushbuttons or with the remote communication software.
DISABLED: The controller will not initiate a callout when a “Fail to Transfer alarm
condition occurs.
7.3.6. AUTO TEST CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when a automated test is initiated at the
controller via the TSC 800 exercise time clock. The callout signal will
reset when the Auto Test condition is terminated.
DISABLED: The controller will not initiate a callout an Auto Test condition is initiated.
7.3.7. MAN TEST CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when a manual test is initiated at the controller
via the TSC 800 pushbuttons or external control switch. The callout
signal will reset when the Manual Test condition is terminated.
DISABLED: The controller will not initiate a callout a Manual Test condition is initiated.
7.3.8. SWITCH NOT IN AUTO CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when the TSC 800 controllers’ operating mode
is Not In Auto” as locally selected via the four position external control
switch. The callout signal will reset when the control switch is returned to
the Auto position.
DISABLED: The controller will not initiate a callout if the TSC 800 controller is not in
the Auto mode of operation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.1 and is the answer not in the manual?

THOMSON TSC 800 - V2.1 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.1
CategoryController
LanguageEnglish

Related product manuals