TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 9 06/04/24 Thomson Technology
45
7.3.2. ATS MODE MENU PASSWORD (PW)
NOTE:
The following features is provided in TSC 800 Software version 2.0 (or
higher). Viewable only in Master Read / Write Mode.
Allows setting of Password Protection restricting access to the ATS Mode Menu as
follows:
ENABLED: Access to initiating/changing any test or operation mode requires a user-
entered password. The password required will be the same as a level 2
(e.g. read/write password level or higher).
DISABLED: The ATS Mode Menu may be entered and changes made/initiated
without the use of a security password.
7.3.3. UTILITY FAIL CALLOUT
NOTE:
The following features are viewable only in Master Read / Write Mode in
TSC 800 Software version 2.0 (or higher).
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when a Utility (Source 1) power failure is
detected. The callout signal will be reset when the Utility (Source 1)
power returns to normal condition.
DISABLED: The controller will not initiate a callout when a Utility (Source 1) power
failure is detected.
7.3.4. LOAD ON GENERATOR CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when the load is connected to the generator
supply. The callout signal will be reset when the load transfers back to
the utility supply.
DISABLED: The controller will not initiate a callout when the load transfers to the
generator supply.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.1 and is the answer not in the manual?

THOMSON TSC 800 - V2.1 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.1
CategoryController
LanguageEnglish

Related product manuals