EasyManuals Logo

THOMSON TSC 800 - V2.1 User Manual

THOMSON TSC 800 - V2.1
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 9 06/04/24 Thomson Technology
47
7.3.9. NODE ADDRESS
Set to unique controller address (1-255) for use with network connected TSC 800
controllers.
NOTE: This programming feature is only active when the remote communication
option is enabled. Default setting for single TSC 800 applications is 1.
7.3.10. SYSTEM VOLTAGE
Set to nominal system voltage as expressed in “phase to phase” voltage. (e.g. A
347/600 volt system would be entered as “600”.) The programmable range of values
is 120V-15,000V.
7.3.11. VOLTAGE SENSING RATIO
For direct voltage sensing wiring connections from 208 to 600 volts, enter a ratio of
“1.0:1”. When potential transformers are utilized for voltage sensing, enter the
transformer ratio. (e.g. When using a 600:120 transformer, enter a ratio of “5.0:1”).
The ratio is programmable in tenths to allow minor correction factors to be used for
non-standard potential transformer ratios.
7.3.12. SYSTEM FREQUENCY
Set to nominal system frequency of either 50Hz or 60Hz.
7.3.13. SYSTEM PHASES
Set to match the power distribution system used on the automatic transfer switch (i.e.
either single phase or 3 phase system).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.1 and is the answer not in the manual?

THOMSON TSC 800 - V2.1 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.1
CategoryController
LanguageEnglish

Related product manuals