8.8 APPENDIX C - Setting table
Notes: - The 26 element, the output relay and LEDs K7...K10, L6...L10 and the binary input IN3...IN42 settings are available only when the concerning I/O
circuits are implemented (MPT, MRI and MID16 modules on Thybus)
Description Parameter Unit Setting range
Set
Base
Relay reference name
Relay nominal frequency - fn
Hz 50 ... 60 step = 10
Relay nominal voltage - Un
V
50 ... 130 step = 1
200 ... 520 step = 1
Relay residual nominal voltage ( direct measurement ) - UEn
V 50 ... 130 step = 1
Relay residual nominal voltage ( calculated measurement )
- UECN = 1.73 * Un
Line VT primary nominal voltage - Unp
V
50 ... 499 step = 1
500 ... 4990 step = 10
5000 ... 49900 step = 100
50000 ... 500000 step = 1000
Residual primary nominal voltage ( phase to phase ) * 1.73
- UEnp
V
50 ... 499 step = 1
500 ... 4990 step = 10
5000 ... 49900 step = 100
50000 ... 500000 step = 1000
Measurements reading mode
RELATIVE | PRIMARY
Language
English | Turkish | Russian | Espanol
Inputs
Binary input IN1
IN1
Logic
Active-ON | Active-OFF
IN1 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN1 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN1 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN1 matching (B)
none
Binary input IN2
IN2
Logic
Active-ON | Active-OFF
IN2 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN2 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN2 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN2 matching (B)
none
Binary input IN3
IN3
Logic
Active-ON | Active-OFF