EasyManua.ls Logo

Thytronic NV10P - Ten Minutes Overvoltage - 59 Uavg for Inductive Vts Versions; Ten Minutes Overvoltage - 59 Uavg [1] for Electronic Sensor Versions; Residual Overvoltage - 59 N for Inductive Vts Versions

Thytronic NV10P
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
NV10P - Manual - 01 - 2015
TECHNICAL DATA
Ten minutes overvoltage - 59Uavg
[1]
for inductive VTs versions
Common confi guration:
Operating logic (Logic59Uavg) AND/OR
Uavg> Element
Defi nite time
First threshold defi nite time (
U
avg
>
def
) 0.50...1.50 U
n
(step 0.01 U
n
)
Time delay (t
Uavg
>
def
) 0...1000 s (step 1 s)
Pickup time according to the reference conditions
[2]
Pickup accuracy ± 1% ± 1% U
n
Time delay accuracy
[3]
5% ± 3 s
Ten minutes overvoltage - 59Uavg
[1]
for electronic sensor versions
Common confi guration:
Voltage measurement type (Utype59Uavg) U
ph-ph
/U
ph-n
Operating logic (Logic59Uavg) AND/OR
Uavg> Element
Defi nite time
First threshold defi nite time (
U
avg
>
def
) 0.50...1.50 U
n
(step 0.01 U
n
/E
n
)
Time delay (t
Uavg
>
def
) 0...1000 s (step 1 s)
Pickup time according to the reference conditions
[2]
Pickup accuracy ± 1% ± 1% U
n
/E
n
Time delay accuracy
[3]
5% ± 3 s
Residual overvoltage - 59N for inductive VTs versions
Common confi guration:
Residual voltage measurement type for 59N - direct/calculated (
3
Vo
Type59N
) U
E
/U
EC
Operation from 74VT external (74VText59N) OFF
/Block
U
E
> Element
U> Curve type (U>
Curve
) DEFINITE/INVERSE
[4]
U
E
> Reset time delay (t
UE>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
59N First threshold defi nite time (
U
E
>
def
) 0.01...0.70 U
En
(step 0.01 U
En
)
U
E
>
def
Operating time (t
UE
>
def
) 0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Inverse time
59N First threshold inverse time (
U
E
>
inv
) 0.01...0.50 U
En
(step 0.01 U
En
)
U
E
>
inv
Operating time (t
UE
>
inv
) 0.10...100.0 s
0.10...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Element
U
E
>>
U
E
>> Reset time delay (t
UE>>RES
)
0.00...100.0 s
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
59N Second threshold defi nite time (
U
E
>>
def
) 0.01...0.70 U
En
(step 0.01 U
En
)
U
E
>>
def
Operating time (t
UE
>>
def
) 0.07...100.0 s
0.07...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
U
E
>> Reduced Operating time
(t
cUE
>>
def
) 0.07...10.00 s (step 0.01 s)
t
cUE
>> Activation time (t
atcUE
>>) 1...60 s (step 1 s)
Pickup time 0.04 s
Dropout ratio 0.95...0.98
Dropout time 0.04 s
Overshoot time 0.03 s
Pickup accuracy ± 1% ± 1% U
En
Operate time accuracy 5% or ± 10 ms
Note 1 The function is based on the measurement of the mean of the three phase voltages of 10 minutes with update every three seconds
Note 2 The pickup time depends on the initial and fi nal value of the input voltage; e.g. with a setting of threshold equal to 1.10 Un:
- with initial value 0 and fi nal value 1.1 Uavg> def (1.1x1.1 = 1.21 Un) the pickup time is 498 s
- with initial value 0.9 Uavg>def (0.9x1.1 = 0.99 Un) and fi nal value 1.1 Uavg>def (1.1x1.1 = 1.21 Un) the pickup time is 285 s
Note 3 Since the aggregate value is updated every 3 s, times are only meaningful in multiples of 3 s
Note 4 The mathematical formula for INVERSE curve is t= (0.5 ∙ t
UE
>
inv
) / [(U
E
/U
E
>
inv
) - 1]
t = operating time (in seconds)
t
UE
>
inv
= operating time setting (in seconds)
U
E
= residual input voltage (direct or calculated)
U
E
>
inv
= threshold setting