EasyManua.ls Logo

Thytronic NV10P - Application Notes about Over-Under Frequency Elements - 81 U and 81 O; Operating Logic for Thresholds Activation with Voltmetric Control

Thytronic NV10P
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
77
NV10P - Manual - 01 - 2015
CHARACTERISTICS
Application notes about over-under frequency elements - 81U and 81O
To ensure compliance with CEI 0-16 italian standard the voltage enabling function is provided
through which the fi rst threshold can be enable / disable, respectively, in the absence / presence of
the signal integrity of the communication network Distributor (digital input set with inverse logic and
f <-f> Control function or communication interface protocol IEC 61850).
For the trip of the fi rst threshold of each element can be enabled by one or more of the following
consensus:
start of residual current second threshold (59N internal element by programming ON the f<&UE>>,
f>&UE>> parameter)
start of residual voltage second threshold (59N external element) acquired by means of binary input
programmed as f<-f> Control (setting ON the f<&DIGIN, f>&DIGIN parameter)
loss of communication network acquired by means of binary input programmed as f<-f> Control
with inverse logic (setting ON the f<&DIGIN, f>&DIGIN parameter)
start of positive sequence undervoltage threshold (27V1 programming ON the f<&27V1, f>&27V1
parameter)
start of negative sequence overvoltage threshold (59V2 programming ON the 59V2 (programming
ON the f<&59V2, f>&59V2 parameter)
start of fi rst threshold of the undervoltage element (27 programming ON the f<&U<, f>&U<
parameter)
loss of communication network from Goose IEC 61850 message programming ON the
f<&rete61850-KO, f>&rete61850-KO parameter.
The parameters listed above are available in the menus inside the menu
Set \ Profi le A(or B) \ Underfrequency - 81U \ f< element \ Voltage control for parameters concern-
ing to the underfrequency element (81U) and within the Set \ Profi le A(or B) \ Overfrequency - 81O \
f> element \ Voltage control menu for parameters concerning to the overfrequency element (81O).
Operating logic for thresholds activation with voltmetric control
Delayed trip 4.0 s
Delayed trip 1.0 s
Delayed trip 0.1 s
ON = Fault (Start 59N and/or 27V1 and/or 59V2 element)
f < 47,5 Hz
V0> threshold
f > 51,5 Hz
Vi > threshold
Vd< threshold
f < 49,8 Hz
f > 50,2 Hz
or
&
V
or
f (Hz)
without fault
f (Hz)
50
81>
81<
t (s)
restrictive thresholds
0.1
49.7 50.3
with fault
t (s)
permissive thresholds
f (Hz)
5047.5
1.0
4.0
51.5
81>>
81<<
Operating logic for thresholds activation with voltmetric control
Delayed trip 4.0 s
Delayed trip 1.0 s
Delayed trip 0.1 s
ON = Fault (Start 59N and/or 27V1 and/or 59V2 element)
f < 47,5 Hz
V0> threshold
f > 51,5 Hz
Vi > threshold
Vd< threshold
f < 49,8 Hz
f > 50,2 Hz
or
&
V
or
f (Hz)
without fault
f (Hz)
50
81>
81<
t (s)
restrictive thresholds
0.1
49.7 50.3
with fault
t (s)
permissive thresholds
f (Hz)
5047.5
1.0
4.0
51.5
81>>
81<<

Table of Contents

Related product manuals