NV10P - Manual - 01 - 2015
MEASURES, LOGIC STATES AND COUNTERS
27 - Counters
27V1 - Counters
59 - Counters
59V2 - Counters
59Uavg - Counters
59N - Counters
81O - Counters
81U - Counters
81R - Counters
74TCS - Counters
CB - Counters
BF - Counters
Partial counters
xx Start partial counter (xx = I>, I>>,...) 0...9999
xx Trip partial counter (xx = I>, I>>,...) 0...9999
xx Block1 partial counter (xx = I>, I>>,...) 0...9999
xx Block2 partial counter (xx = I>, I>>,...) 0...9999
Total counters
xx Start total counter (xx = I>, I>>,...) 0...9999
xx Trip total counter (xx = I>, I>>,...) 0...9999
xx Block1 total counter (xx = I>, I>>,...) 0...9999
xx Block2 total counter (xx = I>, I>>,...) 0...9999
Self test
Lower level diagnostic (MINOR) can be output or ignored; for this purpose the MINOR Fail alarm
parameter can be set ON or OFF inside the Set\Self test relay submenu.
Following anomalies (MINOR) are not relevant (the protective elements continue to work):
Errors concerning the digital fault recorder.
Internal bus.
The self test information are:
Protection and controls ON SERVICE/OUT OF SERVICE
System diagnostic OK/NOT OK
Device diagnostic OK/NOT OK
Program diagnostic OK/NOT OK
Data-base boot OK/NOT OK
Data-base runtime OK/NOT OK
DSP boot OK/NOT OK
DSP run-time OK/NOT OK
Memory boot OK/NOT OK
Memory run-time OK/NOT OK
Data Bus heavy OK/NOT OK
Data Bus minor OK/NOT OK
Oscillography run-time OK/NOT OK
PLC boot OK/NOT OK
PLC run-time OK/NOT OK
Protection I/O assigned verify startup OK/NOT OK
Protection I/O assigned verify run-time major OK/NOT OK
Protection I/O assigned verify run-time minor OK/NOT OK
Total protection I/O assigned not-matching 0
Protection I/O assigned not-matching
PLC I/O assigned not-matching OK/NOT OK
PLC I/O assigned not-matching run-time major OK/NOT OK
PLC I/O assigned not-matching run-time minor OK/NOT OK
Total PLC I/O assigned not-matching 0
PLC I/O assigned not-matching
MMI module Boot OK/NOT OK
MMI module Run-time OK/NOT OK
MRI module Boot OK/NOT OK
MRI module Run-time OK/NOT OK
MID16-1 module Boot OK/NOT OK
MID16-1 module Run-time OK/NOT OK
MID16-2 module Boot OK/NOT OK
MID16-2 module Run-time OK/NOT OK
PT100 module Boot OK/NOT OK
PT100 module Run-time OK/NOT OK
Current loop module Boot OK/NOT OK
Current loop Run-time OK/NOT OK
Oscillography run-time OK/NOT OK
The diagnostic alarms can be allocated to an output relay; for this purpose the Self-test relay pa-
rameter can be set (K1...K6) inside the Set \ Self-test Relay
submenu.
Fault recording - SFR
Recording is triggered by one or more causes (up to 8 simultaneous):
Activation (OFF-ON transition) of any relay programmed for trip of protection or control element
External trigger (binary input programmed as Fault trigger)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•